Product

Circuit Breaker Tester KVCB-12Y

Circuit Breaker Tester is a specialized instrument designed to meet the requirements for testing the action characteristics of various high-voltage switches. It can accurately measure the mechanical dynamic characteristic parameters of high-voltage circuit breakers across different voltage levels, including low-oil, high-oil, vacuum, and sulfur hexafluoride types. For circuit breakers with closing resistance, it can precisely measure the closing resistance and switching waveforms.

Product Description

General Information 

Circuit Breaker Tester is a specialized instrument designed to meet the requirements for testing the action characteristics of various high-voltage switches. It can accurately measure the mechanical dynamic characteristic parameters of high-voltage circuit breakers across different voltage levels, including low-oil, high-oil, vacuum, and sulfur hexafluoride types. For circuit breakers with closing resistance, it can precisely measure the closing resistance and switching waveforms.

Unique Advantage

  • Timing:All 12 common breakers have synchronized opening and closing times, with similar phase characteristics.
  • Reclosing:Each breaker’s closing-opening and opening-closing cycles are measured, including one opening time, one closing time, two opening times, short-circuit duration, and current interruption values.
  • Bounce:This includes the closing bounce time, number of bounces, bounce process details, and bounce waveform for each breaker, as well as the rebound amplitude during opening.
  • Speed:This covers the opening and closing speeds, maximum speed, and the time-travel characteristic curve.
  • Current:This includes the opening and closing current values and the current waveforms for the opening and closing coils.
  • Action Voltage:The machine provides a digital adjustable power supply (DC 30-250V/20A) for testing. It automatically performs low-voltage action tests and measures the action voltage values for each breaker.

 

Technical Data

 

Service condition Input power 220V±10% 50Hz±10%
Atmospheric pressure 86~106kpa ℃
Temperature -10~45℃
Humidity ≦80%RH
Safety Performance Insulation resistance >2MΩ
Dielectric strength Power to chassis frequency voltage withstands 1.5KV, 1 min, no flashover and arcing.
Basic parameters Time Range: 16000.0ms, resolution: 0.1ms
Error: ①200ms within,0.1ms±1d
②200ms above,±2%
③±0.1ms synchronous
Speed Range: 20.00m/s, resolution 0.01m/s
Error:①0~2m/s : ±0.1m/s±1d
②>100m/s, ±0.2m/s±1d
Range Vacuum Circuit Breaker: range-50.0mm, resolution-0.1mm, error-±0.5mm
SF6 Circuit Breaker: range-300.0mm, resolution-0.1mm, error-±2mm
Oil-minimum breaker: range-600.0mm, resolution-0.1mm, error-±2mm
Current Range: 20.00A, resolution: 0.01A
Fracture type 12way metal fracture,6 way closing resistance fracture, 3 -way graphite contact
Output power DC30~250V digitally adjustable /20A (Instantaneous work)
Dimension Host: 360mm×290mm×280mm: accessory:370mm×280mm×220mm
Weight Host:6kg, attachment:9kg
en_USEnglish

Inquiry Now