설명
General Information
Transformer on-load switch tester is a test equipment for testing the on-load tap changer of action sequence and switching time. Transformer On-load Tap Changer Tester is mainly applied to measure the transient waveform, transient time, transient resistance value, three-phase synchronization of transformer on-load tap-changers.
기능
- Test transformers of type Y0, Y, and △, and display resistance values directly.
 - Automatically analyze waveform faults and mark the faults.
 - Automatically adjust resistance values and time ranges based on sampling data.
 - Display synchronization status of three phases for transformer type △.
 - Test with or without winding.
 - Support four-terminal connection mode for high-accuracy resistance measurement.
 - Enable continuous testing to save power-off time.
 - Generate word reports.
 - Equipped with an 800×480 colorized LCD with touch screen and a high-speed printer.
 - Store up to 1000 groups of data and allow saving to USB flash disk.
 
기술 사양
- Three phase constant current source charge,charge current: 3A/1A; 0.6A/0.2A
 - Maximum voltage of the port: 24V
 - Maximum range of transition resistance: 100Ω
 - Measuring range: 1A:4Ω~20Ω 0.2A:10Ω~100Ω
 - Record time of waveform:300ms
 - Sample rate: 30k
 - Resolution of time:0.1ms
 - Resolution of resistance: 0.1Ω
 - Accuracy of transition resistance: ±5% Reading±0.1Ω
 - Accuracy of transient time: ±0.5% Reading±0.2mS
 - Temperature: -10-40℃ Humidity: <85%RH
 