Function |
Grounding resistance, loop resistance, conduction resistance and equipotential connection resistance test; soil resistivity and AC voltage test. |
Power |
DC 9V(Zi-Mn dry battery R14S 1.5V 6 PCS, continuous standby for 300 hours ) |
Back light |
Controllable white screen backlight, suitable for use in dark field. |
Testing method |
precision 4 wire 3wire testing, simple 2 wire test grounding resistance |
Measure method |
Earth Resistance: rated current change-pole method, measurement current 20mA Max |
Soil Resistivity: 4-pole measurement (Wenner method) |
Earth Voltage: average rectification(between P(S)-ES) |
Range |
234 wire method for measuring ground resistance (R):0.000Ω~30000Ω |
Soil resistivity (ρ):0.00Ωm~9000kΩm |
Grounding voltage:AC 0.0~100.0V |
Max. resolution |
234 wire method for measuring ground resistance (R):0.001Ω |
Soil resistivity (ρ):0.01Ωm |
Grounding voltage:0.1V |
Accuracy
|
234 wire method for measuring ground resistance (R):
1.0.000Ω~10.00kΩ: ±2%rdg±5dgt
2.10.0K~100.0kΩ: ±3%rdg±5dgt
3.100.0K~200.0kΩ: ±3.5%rdg±5dgt |
Soil resistivity (ρ):depends on R accuracy
(ρ=2πaR a:1 m~100m;π=3.14) |
Grounding voltage: ±2%rdg±3dgt |
testing voltage wave shape |
sine wave |
Testing frequency |
412Hz、825Hz、1280Hz(Automatic frequency selection) |
Short circuit test current |
AC 20mA max |
Open circuit test voltage |
AC 90V max |
Electrode spacing |
1m~100m |
Shift |
Grounding resistance:0.000Ω~200kΩ Full automatic shift |
Soil resistivity:0.00Ωm~9999kΩm Full automatic shift |
LCD |
6-bit LCD display, white screen backlight |
LCD size |
128mm×75mm |
LCD display size |
124mm×67mm |
Testing indication |
LED flashing indication in measurement.LCD count down.Progress bar chart indication |
charging indication |
When charging, the indicator on the charger is bright red, full of bright green. |
size |
Host machine:Length Width Height 320mm×275mm×145mm |
Outer size:Length Width Height 400mm×245mm×335mm |
test time |
Ground voltage:approx 2times/sec;ground resistance:approx 7times/sec;soil resistivity:approx 7times/sec |
test times |
5000times above ( short circuit test, test 1 time,Stop for 30 seconds and retest. ) |
circuit voltage |
AC 600V below test |
communication port |
With RS232 interface, storage data can be uploaded to the computer and saved to print. |
communication wire |
RS232 communication wire 1pcs, length 1.5m |
Data HOLD |
The “HOLD” symbol indicates data is kept. |
data save |
2000 SET,“MEM”Storage instructions,display “FULL”Indicates that the storage is full. |
overflow display |
Exceeding measuring range overflow function: “OL” icon display |
Interface test |
Recognize interference signal automatically, “NOISE” icon display when interference voltage exceed 5V |
auxiliary grounding test |
Can measure auxiliary earth resistance, 0.00KΩ-30000Ω(100R+rC<50kΩ, 100R+rP<50kΩ) |
Alarm function |
When measuring value exceeds alarm setting value, there is “Toot-toot-toot” alarm hint |
battery voltage |
When low battery , battery voltage low icon will display, reminding to charging battery. |
Automatically power off |
Turn off automatically after standby 15 minutes. |
working current |
Standby: about 25mA (Backlight shut off);
backlight:25mA Max(only backlight consumption);
Measurement: about 150mA (Backlight shut off) |
weight |
Host machine:2.66kg(with battery) |
Total weight:6.88kg(with package) |
Tool box |
The military toolbox is designed to support 200kg. |
Overload protection |
Measure ground resistance :C(H)-E、P(S)-ES between each port AC 280V/3sec |
Insulation resistance |
20MΩ above(between circuit and shell 500V) |
Withstand voltage |
AC 3700V/rms(between circuit and shell) |
Electromagnetic features |
IEC61326(EMC) |
Protection type |
IEC61010-1(CAT Ⅲ 300V、CAT IV 150V、pollution class2);
IEC61010-031;IEC61557-1(ground resistance);IEC61557-5(soil resistivity);JJG 366-2004(ground resistance meter)。 |