KV-HIPOT-Logo-PNG

Product

Transformer on-load switch tester KVYZ-5000

Transformer On-load Tap Changer Tester is mainly applied to measure the  transient waveform,  transient time, transient resistance value, three-phase synchronization of transformer on-load tap-changers.

Product Description

General Information 

Transformer on-load switch tester is a test equipment for testing the on-load tap changer of action sequence and switching time. Transformer On-load Tap Changer Tester is mainly applied to measure the  transient waveform,  transient time, transient resistance value, three-phase synchronization of transformer on-load tap-changers.

 

Feature

  • Test transformers of type Y0, Y, and △, and display resistance values directly.
  • Automatically analyze waveform faults and mark the faults.
  • Automatically adjust resistance values and time ranges based on sampling data.
  • Display synchronization status of three phases for transformer type △.
  • Test with or without winding.
  • Support four-terminal connection mode for high-accuracy resistance measurement.
  • Enable continuous testing to save power-off time.
  • Generate word reports.
  • Equipped with an 800×480 colorized LCD with touch screen and a high-speed printer.
  • Store up to 1000 groups of data and allow saving to USB flash disk.

 

Technical Specification

  • Three phase constant current source charge,charge current: 3A/1A; 0.6A/0.2A
  • Maximum voltage of the port: 24V
  • Maximum range of transition resistance: 100Ω
  • Measuring range: 1A:4Ω~20Ω 0.2A:10Ω~100Ω
  • Record time of waveform:300ms
  • Sample rate: 30k
  • Resolution of time:0.1ms
  • Resolution of resistance: 0.1Ω
  • Accuracy of transition resistance: ±5% Reading±0.1Ω
  • Accuracy of transient time: ±0.5% Reading±0.2mS
  • Temperature: -10-40℃ Humidity: <85%RH
viVietnamese

Inquiry Now