Mô tả
Overview
Battery Discharge Test Unit is used to perform discharge testing which is the only verifiable method to determine actual capacity of battery systems. Whether you proceed the loading test , discharge testing , acceptance testing, battery capacity testing, KV Hipot can provides a full series of customzied DC load banks with many different models. They covers a wide voltage range from 10V to 600V which is widely used on various fields . With optional cell voltage monitor (CVM), discharge data of each cell battery can be monitored directly connecting with battery load bank . The data software can provide user with data report and data graph.
Feature
- Constant current discharge without the need for constantly adjustingduring testing .
- Optional wireless cell voltage monitorenables real-time monitors uncommon cell voltages and configurations
- Four testconditions for discharge auto shut-down: battery string votalge , discharge time, discharge capacity, cell voltage
- Intelligent SCM ARM control, 7 inch1024*600 LCD display with capacitive touch control operation
- Multi-function protection such as overvoltage , undervoltage stop, reverse connection , overtemperature protection , with LCD prompt and buzzer alarm.
- Easily expensable for higher discharge current in parallel connection of master slave mode .
- Accurate data measurement and vivid graphsof PC data management software
- Safe circuits avoids damage to battery during measurement
- Automatically fan run during the test conducted
- Powerful management software for data analysis and report generation
- Optional online compensated charging/discharging can be carried out
Technical Specification
Discharge Voltage Range | DC 10-132V |
Discharge Current Range | 0-100A |
Accuracy | Current ±1%;
Group voltage ≤±0.1% |
Discharge Pattern | Constant current discharge |
Display | 7 inch touch capacitive LCD |
PC Connection | RS485 and USB interface |
Data Storage | 16G |
Cooling | Fan forced cooling |
Power Supply | 220V 50Hz ± 10% |
Noise | ﹤75dB |
Optional cell voltage monitor | Each cell voltage monitor can monitor 12 cell batteries.
Each tester can equipped with 25 cell voltage monitor (CVM), at most of 300 cell battieres. |
Over-protection | Over-voltag ,under-voltage,reverse connection protection , over- temperature 65℃ protection, with LDC display and buzzing alarm |
Working Temperature | -5~50℃ |
Storage Temperature | -40~70℃ |