KV-6000A Transformer Capacitance Tan-delta Tester is a automatic on-site tester that is designed to measure dielectric loss(tgδ)and the capacitance (Cx) of electric equipment. The measure result can be displayed on the LCD screen and printed by micro-printer .It’s suitable for testing on transformer, capacitor, insulating bush, CT/PT, MOA .
Overview
KV-6000A Transformer Capacitance Tan-delta Tester is a automatic on-site tester that is designed to measure dielectric loss(tgδ)and the capacitance (Cx) of electric equipment. The measure result can be displayed on the LCD screen and printed by micro-printer .It’s suitable for testing on transformer, capacitor, insulating bush, CT/PT, MOA .
Features
Technical parameter
♦ Accuracy: Cx: ±(read ×1%+1pF)
tgδ: ±(read ×1%+0.00040)
♦ Anti interference: Frequency conversion anti interference, under 200% interference, still can reach above accuracy.
♦ Capacitance range:Inner HV: 3pF~60000pF/10kV 60pF~1μF/0.5kV
Outside HV: 3pF~1.5μF/10kV 60pF~30μF/0.5kV
Resolution: Max. 0.001pF,4 significant figures
♦ Tgδ range: unlimited, resolution: 0.001%, capacitance, inductance, resistance can be identify automatically.
♦ Test current range: 10μA~1A
♦ Inner HV:Setting voltage range: 0.5~10kV
Max.Output current: 200mA
Increase/decrease voltage: continuous slide regulating.
Test frequency: 45, 50, 55 single frequency
45/55Hz auto double frequency conversion
Frequency precision: ±0.01Hz
♦ Outside HV: Positive connection max. test current 1A, Power frequency or frequency conversion 40-70Hz
Negative connection max. test current: 10kV/1A, power frequency or frequency conversion 40-70Hz
♦ CVT self excitation LV output: voltage 3~50V,current 3~30A
♦ Measuring duty: about 30s,it depend on measuring methods.
♦ Input power supply: 180V~270VAC,50Hz±1%,local supply or by generator.
♦ Communication interface: RS232.
♦ Printer: Build-in thermal printer.
♦ Environmental temperature: -10℃~50℃
♦ Relative humidity: <90%
♦ Oversize: 463×362×350mm
♦ Weight: 29kg