| Function | 
Grounding resistance, loop resistance, conduction resistance and equipotential connection resistance test; soil resistivity and AC voltage test. | 
| Power | 
DC 9V(Zi-Mn dry battery R14S 1.5V 6 PCS, continuous standby for 300 hours ) | 
| Back light | 
Controllable white screen backlight, suitable for use in dark field. | 
| Testing method | 
precision 4 wire 3wire  testing, simple 2 wire test grounding resistance | 
| Measure method | 
Earth Resistance: rated current change-pole method, measurement current 20mA Max | 
| Soil Resistivity: 4-pole measurement (Wenner method) | 
| Earth Voltage: average rectification(between P(S)-ES) | 
| Range | 
234 wire method for measuring ground resistance (R):0.000Ω~30000Ω | 
| Soil resistivity (ρ):0.00Ωm~9000kΩm | 
| Grounding voltage:AC 0.0~100.0V | 
| Max. resolution | 
234 wire method for measuring ground resistance (R):0.001Ω | 
| Soil resistivity (ρ):0.01Ωm | 
| Grounding voltage:0.1V | 
|  
   
  
  
Accuracy 
  
  
   | 
234 wire method for measuring ground resistance (R):
 1.0.000Ω~10.00kΩ:  ±2%rdg±5dgt 
2.10.0K~100.0kΩ:    ±3%rdg±5dgt 
3.100.0K~200.0kΩ:   ±3.5%rdg±5dgt  | 
| Soil resistivity (ρ):depends on R accuracy
 (ρ=2πaR  a:1 m~100m;π=3.14)  | 
| Grounding voltage: ±2%rdg±3dgt | 
| testing voltage wave shape | 
sine wave | 
| Testing frequency | 
412Hz、825Hz、1280Hz(Automatic frequency selection) | 
| Short circuit test current | 
AC 20mA max | 
| Open circuit test voltage | 
AC 90V max | 
| Electrode spacing | 
1m~100m | 
| Shift | 
Grounding resistance:0.000Ω~200kΩ Full automatic shift | 
| Soil resistivity:0.00Ωm~9999kΩm Full automatic shift | 
| LCD | 
6-bit LCD display, white screen backlight | 
| LCD size | 
128mm×75mm | 
| LCD display size | 
124mm×67mm | 
| Testing indication | 
LED flashing indication in measurement.LCD count down.Progress bar chart indication | 
| charging indication | 
When charging, the indicator on the charger is bright red, full of bright green. | 
| size | 
Host machine:Length Width Height 320mm×275mm×145mm | 
| Outer size:Length Width Height 400mm×245mm×335mm | 
| test time | 
Ground voltage:approx 2times/sec;ground resistance:approx 7times/sec;soil resistivity:approx 7times/sec | 
| test times | 
5000times above ( short circuit test, test 1 time,Stop for 30 seconds and retest. ) | 
|  circuit voltage | 
AC 600V below test | 
| communication port | 
With RS232 interface, storage data can be uploaded to the computer and saved to print. | 
| communication wire | 
RS232 communication wire 1pcs, length 1.5m | 
| Data HOLD | 
The “HOLD” symbol indicates data is kept. | 
| data save | 
2000 SET,“MEM”Storage instructions,display “FULL”Indicates that the storage is full. | 
| overflow display | 
Exceeding measuring range overflow function: “OL” icon display | 
| Interface test | 
Recognize interference signal automatically, “NOISE” icon display when interference voltage exceed 5V | 
| auxiliary grounding test | 
Can measure auxiliary earth resistance, 0.00KΩ-30000Ω(100R+rC<50kΩ, 100R+rP<50kΩ) | 
| Alarm function | 
When measuring value exceeds alarm setting value, there is “Toot-toot-toot” alarm hint | 
| battery voltage | 
When low  battery , battery voltage low icon will display, reminding to charging battery. | 
| Automatically power off | 
Turn off automatically after standby 15 minutes. | 
| working current | 
Standby: about 25mA (Backlight shut off);
 backlight:25mA Max(only backlight consumption); 
Measurement: about 150mA (Backlight shut off)  | 
| weight | 
Host machine:2.66kg(with battery) | 
| Total weight:6.88kg(with package) | 
| Tool box | 
The military toolbox is designed to support 200kg. | 
| Overload protection | 
 Measure ground resistance :C(H)-E、P(S)-ES between each port AC 280V/3sec | 
| Insulation resistance | 
20MΩ above(between circuit and shell 500V) | 
| Withstand voltage | 
AC 3700V/rms(between circuit and shell) | 
| Electromagnetic features | 
IEC61326(EMC) | 
| Protection type | 
IEC61010-1(CAT Ⅲ 300V、CAT IV 150V、pollution class2);
 IEC61010-031;IEC61557-1(ground resistance);IEC61557-5(soil resistivity);JJG 366-2004(ground resistance meter)。  |