{"id":6665,"date":"2026-09-23T22:22:59","date_gmt":"2026-09-23T14:22:59","guid":{"rendered":"https:\/\/kvhipot.com\/?p=6665"},"modified":"2026-09-23T22:23:01","modified_gmt":"2026-09-23T14:23:01","slug":"33-kv-kabel-uchun-vlf-hipot-testi-uchun-qanday-kuchlanishni-ishlatish-kerak","status":"publish","type":"post","link":"https:\/\/kvhipot.com\/uz\/what-vlf-hipot-test-voltage-should-you-use-for-a-33-kv-cable\/","title":{"rendered":"33 kV kabeli uchun qanday VLF hipot test kuchlanishini ishlatish kerak?"},"content":{"rendered":"<h1 class=\"wp-block-heading\"><\/h1><p>\u201c33 kV kabel\u201d so\u2018zi asosida test kuchlanishini tanlash orqali elektr simsizligi uzilishi mumkin, u tekshirilmaydi yoki mulk egasi qabul qila olmaydigan hisobot tayyorlanishi mumkin.<\/p><p>Har bir 33 kV kabeli uchun universal sinov kuchlanishi mavjud emas. Agar nomlovchi belgida 19\/33 (36) kV ko\u02bbrsatilgan bo\u02bblsa va tasdiqlangan tartibda 3U\u2080 sinusoidal VLF belgilangan bo\u02bblsa, hisoblangan daraja 57 kV RMS yoki taxminan 81 kV cho\u02bbqqi kuchlanishi bo\u02bbladi. 18\/30 (36) kV kabeli boshqacha natija keltirib chiqaradi.<\/p><figure class=\"wp-block-image size-large is-resized\"><img fetchpriority=\"high\" decoding=\"async\" width=\"1024\" height=\"673\" src=\"https:\/\/kvhipot.com\/wp-content\/uploads\/2026\/09\/VLF-Hipot-Tester-1024x673.gif\" alt=\"\" class=\"wp-image-6668\" style=\"width:469px;height:auto\" srcset=\"https:\/\/kvhipot.com\/wp-content\/uploads\/2026\/09\/VLF-Hipot-Tester-1024x673.gif 1024w, https:\/\/kvhipot.com\/wp-content\/uploads\/2026\/09\/VLF-Hipot-Tester-700x460.gif 700w, https:\/\/kvhipot.com\/wp-content\/uploads\/2026\/09\/VLF-Hipot-Tester-768x505.gif 768w, https:\/\/kvhipot.com\/wp-content\/uploads\/2026\/09\/VLF-Hipot-Tester-18x12.gif 18w\" sizes=\"(max-width: 1024px) 100vw, 1024px\" \/><\/figure><p>Hisob-kitob oddiy; hisob-kitobning qo\u2018llanilishini aniqlash muhim qismdir. Ushbu qo\u2018llanmada U\u2080ni aniqlash, boshqaruvchi test tartibini tanlash, RMS va cho\u2018qqi kuchlanishini ajratish, testerni kabelli o\u2018tkazuvchanlikka nisbatan tekshirish va qo\u2018shimcha sinovlar natijasini tasdiqlamay, natijani tushunish mumkinligi tushuntiriladi.<\/p><h2 class=\"wp-block-heading\">57 kV RMS har bir 33 kV kabel uchun to'g'ri VLF test kuchlanishi bo'ladimi?<\/h2><p>Yo'q. Ko'pincha keltiriladigan 57 kV qiymati 19 kV fazadan erga uzatiladigan kuchlanishning uch baravarini ko'paytirish natijasidir. U faqat kabelning kuchlanish ko'rsatkichi va tasdiqlangan sinov tartibi ushbu hisob-kitobni tasdiqlasa amal qiladi.<\/p><p>\u201c33 kV\u201d belgisining to\u2018liqligi mavjud emas, chunki u kabelning to\u2018liq nominal kuchlanish belgisidan ko\u2018ra tizimning fazalardan fazaga o\u2018tkaziladigan kuchlanishini anglatishi mumkin. Nominal jihatdan o\u2018xshash tarmoqlarga ulangan ikkita loyiha turli kabel belgilari yoki turli egalar talablaridan foydalanishi mumkin.<\/p><p>Sinusoid shaklidagi to\u2018lqin uchun hisoblash misollari quyidagilar:<\/p><figure class=\"wp-block-table\"><table><thead><tr><th>Misol kabel belgilash<\/th><th>U\u2080 hisob-kitobda ishlatilgan<\/th><th>Misol multiplikatori<\/th><th>Hisoblangan RMS kuchlanish<\/th><th>Sinusoidal peak ekvivalent<\/th><\/tr><\/thead><tbody><tr><td>18\/30 (36) kV<\/td><td>18 kV<\/td><td>3U\u2080<\/td><td>54 kV RMS<\/td><td>Taxminan 76,4 kV cho\u02bbqqisi<\/td><\/tr><tr><td>19\/33 (36) kV<\/td><td>19 kV<\/td><td>3U\u2080<\/td><td>57 kV RMS<\/td><td>Taxminan 80,6 kV maksimal kuchlanish<\/td><\/tr><\/tbody><\/table><\/figure><p>Ushbu misollar universal test ko\u2018rsatmalaridir emas, matematik misollardir. Multiplikator va davomiylik ko\u2018rsatkichlari amaldagi standart, loyiha tavsifi, kabellar ishlab chiqaruvchisi va tasdiqlangan test rejasidan kelib chiqishi kerak. O\u2018ziga xos to\u2018lqin yoki test turiga tegishli standart jadval o\u2018rnini hisoblangan qiymat bilan almashtirmang.<\/p><p>Test qurilmasiga kuchlanish kiritishdan oldin quyidagilarni qayd qiling:<\/p><ul><li>U\u2080\/U (U\u2098) kabi to\u02bbliq kabel belgilash<\/li>\n\n<li>Izolyatsiya turi va kabel ishlab chiqaruvchisi<\/li>\n\n<li>Kabellarning uzunligi va taxminiy yoki o\u2018lchangan o\u2018tkazuvchanlik<\/li>\n\n<li>Bosh va tugatish joylari soni va turlari<\/li>\n\n<li>O\u2018rnatish, qabul qilish yoki texnik xizmat ko\u2018rsatish maqsadlari<\/li>\n\n<li>VLF to\u2018lqin shakli va chastotasi<\/li>\n\n<li>Qo\u2018llaniladigan standart nashr va loyiha spetsifikatsiyasi<\/li>\n\n<li>Talab qilinadigan test davomiyligi va qabul qilish organi<\/li><\/ul><p>Agar ushbu ma\u2019lumotlarning birortasi noma\u2019lum bo\u201clsa, testdan oldin mas\u2019ul muhandis ularni hal qilishi kerak. \u201dXavfsirab\u201d kuchlanishni oshirish kabel ma\u2019lumotlari yetishmagan holatni o\u2018rnini bosadigan xavfsiz usul emas.<\/p><h2 class=\"wp-block-heading\">33 kV kabel nomli plakatdagi U\u2080, U va U\u2098 nimalarni anglatadi?<\/h2><p>U\u2080, U va U\u2098 turli voltaj munosabatlarini ifodalaydi. Ularni chalkashtirib yuborish noto'g'ri VLF sozlamasining eng keng tarqalgan sabablaridan biridir.<\/p><ul><li><strong>U\u2080<\/strong>\u00a0bu kabelning nominal quvvat chastotasi bo\u2018yicha kuchlanishi bir uzatkich va er yoki metall ekran o\u2018rtasidagi masofadir.<\/li>\n\n<li><strong>U<\/strong>\u00a0bu - oqim o\u2018tkazuvchilari o\u2018rtasidagi nominal kuchlanishdir.<\/li>\n\n<li><strong>U\u2098<\/strong>\u00a0kabellarning va uning aksessuarlarining dizayni uchun mo'ljallangan eng yuqori tizim voltaji hisoblanadi.<\/li><\/ul><p>19\/33 (36) kV kabeli uchun U\u2080 qiymati 19 kV, U qiymati 33 kV va U\u2098 qiymati 36 kV ni tashkil qiladi. Agar tasdiqlangan tartib-taomillar U\u2080 qiymatining ko\u2018paytmasi sifatida ifodalangan sinov darajasini talab qilsa, hisob-kitob 19 kV dan boshlanadi \u2014 33 kV dan emas.<\/p><p>Tanish hisob-kitob&nbsp;<code>33 kV \u00f7 \u221a3 \u2248 19,05 kV<\/code>&nbsp;bu uch fazali tizimda fazalardan erga uzatiladigan kuchlanish munosabatini tushuntirishga yordam berishi mumkin. Biroq, u nomlovchi belgini yoki kabel haqidagi ma\u2019lumotnomani almashtirmasligi kerak. Kabelning kuchlanish belgilari va erga ulanguvchi sharoitlar bozorlar bo\u2018yicha farq qiladi va nominal 33 kV tarmoq har bir o\u2018rnatilgan kabelning 19\/33 (36) kV belgilanganini anglatmasligi kerak.<\/p><p>Buni dalillar tartibini qo\u2018llang:<\/p><ol><li>Kabellarning qobiqidagi belgilarni yoki ishlab chiqaruvchining ma\u2019lumotnomalarini o\u2018qing.<\/li>\n\n<li>Tarmoq va zaryadlash moslamalari joylashuvi tasdiqlang.<\/li>\n\n<li>Loyihaviy kabellar jadvalini va aksessuarlarning xarakteristikalarini tekshiring.<\/li>\n\n<li>Ruxsat etilgan dala sinovlari tartibini aniqlang.<\/li>\n\n<li>Test kuchlanishini hisoblashdan oldin har qanday farqni bartaraf qiling.<\/li><\/ol><p><\/p><h2 class=\"wp-block-heading\">Qaysi standart va sinov maqsadlari voltaj va davomiylikka ta'sir qiladi?<\/h2><p>Kabellarning sinov turi o\u2018zi test rejasini belgilamaydi. Shuningdek, boshqaruv hujjatida kabellarning qurilishi, sinov usuli, to\u2018lqin shakli, hayot aylanishi bosqichi va testning qo\u2018llab-quvvatlashni ko\u2018zda tutishi kerak bo\u2018lgan qarorlar ham belgilanishi kerak.<\/p><p><a href=\"https:\/\/standards.ieee.org\/ieee\/400.2\/11049\/\">IEEE 400.2-2024<\/a>&nbsp;1 Hz dan past VLF energizatsiyasi yordamida himoyalangan elektr kabellar tizimlarining ishonchliligini va diagnostik tekshiruvlarini o\u2018z ichiga oladi. 2013 yilgi nashrni o\u2018rnini bosadi.&nbsp;<a href=\"https:\/\/standards.ieee.org\/ieee\/400\/7618\/\">IEEE 400-2023<\/a>&nbsp;5 kV va undan yuqori quvvatga ega himoyalangan kabellar tizimlari uchun mavjud bo\u2018lgan soha sinovlari usullarini baholash uchun kengroq qo\u2018llanma hisoblanadi.<\/p><p><a href=\"https:\/\/webstore.iec.ch\/en\/publication\/95394\">IEC 60502-2:2014+A1:2024<\/a>&nbsp;U\u208b36 kV gacha bo'lgan ekstrudirovka qilinadigan izolyatsiyalangan elektr kabellarining qurilishi, o'lchamlari va sinov talablarini qamrab oladi. Loyiha ham utility, milliy, shartnoma, kabel ishlab chiqaruvchi yoki aksessuarlarni ishlab chiqaruvchi talablarni ham belgilashi mumkin.<\/p><p>Test maqsadi muhandislik savolini o\u2018zgartiradi:<\/p><figure class=\"wp-block-table\"><table><thead><tr><th>Test maqsadi<\/th><th>Tipik savol<\/th><th>Testdan oldin mavjud bo'lgan dalillar<\/th><th>Nega rejalar farq qilishi mumkin<\/th><\/tr><\/thead><tbody><tr><td>O\u2018rnatish tekshiruvi<\/td><td>Kabellarning transport yoki o\u2018rnatish davomida shikastlanishi bormi?<\/td><td>Yangilangan kabel ma'lumotlari, o'rnatish yozuvlari va kabel uchlari hali ham mavjud bo'lishi mumkin<\/td><td>Accessuarlar va yakuniy sxem konfiguratsiyasi hali to'liq bo'lmasligi mumkin.<\/td><\/tr><tr><td>Qabul testi<\/td><td>To\u2018ldirilgan kabel tizimi quvvatlanishdan oldin qabul qilinadimi?<\/td><td>Kabellar, ulagichlar, tugatishlar, o\u2018rnatish va ishga tushirish yozuvlari<\/td><td>To'liq sxema va ishlab chiqarish jarayonlari ko'rib chiqilmoqda<\/td><\/tr><tr><td>Ta'mirlash testi<\/td><td>Xizmat ko\u2018rsatish yoshidagi qurilma egasining dasturi asosida ishlay oladimi?<\/td><td>Xizmat tarixi, avvalgi testlar, nosozliklar, yuk va uzilishlar oqibatlari<\/td><td>Yosh, noaniqlik va muvaffaqiyatsizlik oqibatlari aktivga xos qarorni talab qiladi<\/td><\/tr><\/tbody><\/table><\/figure><p>Standartlar va egalar o\u201crtasida terminologiya farq qilishi mumkin, shuning uchun usul bayonida ushbu loyiha uchun \u201do\u201crnatish\u201d, \u201cqabul qilish\u201d va \u201cta\u2019mirlash\u201d tushunchalari nima deganini aniqlash lozim.<\/p><p>Birinchi nashrdagi kuchlanishni, boshqa hujjatdagi davomiylikni va uskunalar haqidagi ma\u2019lumotnomadan kelib chiqqan to\u2018lqin shaklini birlashtirmang. Har bir test parametriga oid aniq manbani qayd qiling. Bizning VLF kabel sinov standartlari qo\u2018llanmasi standartlarni, to\u2018lqin shaklini, kalibrlash va moslik hujjatlarini bir hujjat to\u2018plami sifatida qanday ko\u2018rib chiqishni tushuntiradi.<\/p><h2 class=\"wp-block-heading\">U\u2080 ni VLF RMS va cho\u02bbqqi kuchlanishiga qanday aylantirasiz?<\/h2><p>Sinusoid VLF chiqishi uchun RMS va pik markazlari qiymatlari boshqa sinusoidal to\u2018lqinlar uchun ishlatiladigan matematik munosabatlar bilan bog\u2018liq:<\/p><pre class=\"wp-block-code\"><code>Vpeak = Vrms \u00d7 \u221a2\nVrms = Vpeak \u00f7 \u221a2\n<\/code><\/pre><p>Agar tasdiqlangan sinov darajasi 3U\u2080 bo\u2018lsa va U\u2080 19 kV bo\u2018lsa:<\/p><pre class=\"wp-block-code\"><code>3 \u00d7 19 kV = 57 kV RMS\n57 kV \u00d7 1,414 = 80,6 kV cho\u02bbqqi\n<\/code><\/pre><p>Agar U\u2080 qiymati 18 kV bo\u2018lsa:<\/p><pre class=\"wp-block-code\"><code>3 \u00d7 18 kV = 54 kV RMS\n54 kV \u00d7 1,414 = 76,4 kV cho\u02bbqqi\n<\/code><\/pre><p>Konversiya faqat sinyal to\u2018lqiniga tegishli. Avtomatik ravishda qo\u2018llanilmasin&nbsp;<code>\u221a2<\/code>&nbsp;kosin-tekis, tekis yoki boshqa VLF to\u2018lqinli shaklga. Amaldagi test kuchlanishi qanday ifodalanishini va displeyda qanday ma\u2019lumotlar keltirilishini protsedura va asbob hujjatlari belgilashi kerak.<\/p><p>Testdan oldin to'rtta savolga javob bering:<\/p><ol><li>Loyihada sinusoidal yoki boshqa VLF to\u2018lqinli shakl belgilanganmi?<\/li>\n\n<li>Talab qilingan kuchlanish RMS, pik yoki boshqa belgilangan asosda ko\u2018rsatilganmi?<\/li>\n\n<li>Sinovchi RMS, cho\u02bbqqi yoki ikkalasini ham ko\u2018rsatadimi?<\/li>\n\n<li>Kalibrlash sertifikati ishlatiladigan kuchlanish diapazoni va o\u2018lchash asoslarini qamrab oladimi?<\/li><\/ol><p>\u201c80 kV\u201d belgisi qo\u2018yilgan tester model nomidan ajratib olinishi mumkin emas. Taxminan 80,6 kV maksimal kuchlanish talabining misol ko\u2018rsatmasi matematik jihatdan 80 kV dan oshib ketadi, bundan tashqari nashr etilgan kuchlanish maksimal yoki RMS qiymatiga qarab va ushbu birlik kabelning sig\u2018imida ushbu kuchlanishni saqlab qolish qobiliyatiga qarab ishonch hosil qilish mumkin. Talabni uskunaga moslashtirish uchun uning ishlab chiqaruvchining aniq belgilanishi va konfiguratsiya uchun maxsus yuk jadvalini ko\u2018rib chiqing.<\/p><p>Quyidagi VLF testerining texnik xususiyatlari RMS, cho\u02bbqqi kuchlanishi, shakli, chastotasi va yuk qobiliyatini batafsilroq tushuntirish uchun qanday ahamiyat kasb etishini ko\u02bbring.<\/p><h2 class=\"wp-block-heading\">Sinusoidal va kosin-burchakli VLF to\u2018lqinlarining shakllari bir xil sinov qiymatlari ishlatadimi?<\/h2><p>Buni shart emas. Ikkalasi ham VLF shaklidagi to\u2018lqinlar bo\u2018lsa-da, ularning kuchlanish aniqlashlari, stress taqsimoti, sinov darajalari va diagnostika mosligi tegishli tartib-taomillar asosida belgilanishi kerak.<\/p><p>Sinusoid VLF manbai past chastotali sinus to\u2018lqinini hosil qiladi. Ushbu to\u2018lqin shakli taniqli RMS-to-peak (o\u2018rtacha kuchlanish) dan chiqishga moslashuvchan bo\u2018lib, mos keladigan tan delta yoki qisman chiqish tizimlari uchun energiyani taqsimlash manbai sifatida keng qo\u2018llaniladi.<\/p><p>Kosinus-tekislikli manba shaklidagi o\u2018zgarishlar orqali polaritetini o\u2018zgartiradi va aylanishning ayrim qismlarida voltajni boshqacha tarzda saqlaydi. U boshqa ko\u2018rinishdagi izga ega bo\u2018lgan sinus to\u2018lashi sifatida ko\u2018rilmasligi kerak. Voltaj qiymatini bir to\u2018lqinli jadvaldan boshqasiga o\u2018tkazish, mo\u2018ljallangan tartibdan farqli elektr stressni qo\u2018llashi mumkin.<\/p><p><em>To\u2018lqin shakli va o\u2018lchash usuli test maqsadiga mos bo\u2018lishi kerak; qarshilik, tan delta va qisman chiqish sinovlari bir xil savolga javob bermaydi.<\/em><\/p><p>Shuning uchun test hisoboti quyidagicha bo\u2018lishi kerak:<\/p><ul><li>To\u2018lqin shakli turi<\/li>\n\n<li>Nominal va haqiqiy chastota<\/li>\n\n<li>Asbob tomonidan ko\u2018rsatilgan kuchlanish asoslari<\/li>\n\n<li>Maqsad va erishilgan voltaj<\/li>\n\n<li>Rampa va ushlab turish ketma-ketligi<\/li>\n\n<li>Test davomiyligi<\/li>\n\n<li>Kabelli o\u2018tkazuvchanlik yoki yukni taxmin qilish<\/li>\n\n<li>Muvofiq tartib va nashr<\/li><\/ul><p>\u201cIEEE talablariga mos bo\u201dlgan to\u2018lqin\u201d iborasi yetarli emas. Qondirish uchun uskunaning konfiguratsiyasi, test sozlamalari, kalibrlash dalillari, kabel tizimi va soha amaliyotlari tegishli talablarga mos bo\u2018lishi kerak.<\/p><h2 class=\"wp-block-heading\">33 kV XLPE kabelli kabel VLF, DC yoki rezonansli AC bilan sinovdan o\u2018tkazilishi kerakmi?<\/h2><p>O\u2018rnatilgan XLPE yoki EPR kabellar tizimi uchun VLF chidamliligi odatiy tarzda belgilab qo\u2018yilgan soha usulidir, ammo to\u2018g\u2018ri tanlov hali ham tasdiqlangan dasturga bog\u2018liq. Extrusionli izolyatsiya qilingan AC kabellar uchun yuqori kuchlanishli DC simini standart alternativ sifatida ko\u2018rsatish faqat DC sinov apparati mavjudligi tufayli mumkin emas.<\/p><p>Bu usullar turli savollarga javob beradi va turli bosimlar tug'diradi:<\/p><figure class=\"wp-block-table\"><table><thead><tr><th>Metod<\/th><th>Tahlil qilish uchun maqbul foydalanish<\/th><th>Asosiy cheklov<\/th><\/tr><\/thead><tbody><tr><td>VLF qarshiligi<\/td><td>Shaffof kabel tizimi belgilangan past chastotali AC kuchlanishi va vaqtni bardosh bera oladimi<\/td><td>Pass\/fail natijasi har qanday nosozlikni aniqlamaydi yoki qurilmaning qolgan ishlash muddatini taxminlamaydi.<\/td><\/tr><tr><td>VLF tan delta<\/td><td>To'plamli izolyatsiya yo'qotishi, fazalarni taqqoslash va tegishli diagnostika tartibi doirasida holat tendensiyalari<\/td><td>Tarjima uchun bazaviy qiymatlar, voltaj bosqichlari, kabel turi va taqqoslovchi ma'lumotlar kerak bo'ladi.<\/td><\/tr><tr><td>VLF qisqa tutashuvlari<\/td><td>PD faoliyati va tegishli tizim bilan mumkin bo\u2018lgan nosozliklar joyi<\/td><td>O\u2018rnatish, shovqinsizlantirish, aksessuarlar, kalibrlash va ekspert tushuntirishlari juda muhimdir.<\/td><\/tr><tr><td>Resonans yoki boshqa doimiy AC<\/td><td>Doimiy AC manbai talab qilingan tasdiqlangan bardoshlik yoki diagnostika ishlarida qo\u2018llaniladi.<\/td><td>Asboblar hajmi va maydon logistikasi kattaroq bo\u2018lishi mumkin, ayniqsa yuqori sig\u2018imli o\u2018tkazgichlar uchun.<\/td><\/tr><tr><td>Yuqori kuchlanishli DC<\/td><td>Laminatli dielektrik AC kabellari tizimlari, agar ularga tegishli tartib yoki boshqa maxsus vakolatli vazifalar asosida ishlov berilsa<\/td><td>Bu XLPE\/EPR kabelli tizimlarni VLF tekshiruvi uchun universal alternativ emas.<\/td><\/tr><\/tbody><\/table><\/figure><p><a href=\"https:\/\/standards.ieee.org\/ieee\/400.1\/6967\/\">IEEE 400.1-2018<\/a>&nbsp;ikki qatlamli dielektrik himoyalangan AC kabelli tizimlarning yuqori kuchlanishli DC maydonini sinovdan o\u2018tkazishga mo\u2018ljallangan.&nbsp;<a href=\"https:\/\/standards.ieee.org\/ieee\/400.3\/5316\/\">IEEE 400.3-2022<\/a>&nbsp;qoriladigan elektr kabel tizimlarining maydonli qisqa oqimli diagnostik tekshiruvlarini qamrab oladi.<\/p><p>Uchta noto\u2018g\u2018ri da\u2019volardan qoching:<\/p><ul><li>VLF chidamliligi kabelning suv toshmasligini to\u2018g\u2018ridan-to\u2018g\u2018ri isbotlamaydi.<\/li>\n\n<li>VLF tekshiruvi bo\u2018g\u2018imlar va tugunlarning nosozsiz ekanligini isbotlamaydi.<\/li>\n\n<li>DC sinovi har bir kabellarda avtomatik ravishda zararli yoki eskirgan degani emas; uning mosligi kabelning qurilishi va tartib-taomillariga bog\u2018liq.<\/li><\/ul><p>Yaxshi qaror \u201cQaysi usul eng yaxshisi?\u201d emas, \u201cBu kabel tizimi va ushbu texnik xizmat ko\u201drsatish yoki ishga tushirish qarorlari uchun qanday usul dalillarni keltirib chiqaradi?\u201d<\/p><h2 class=\"wp-block-heading\">VLF testeri kabelning kondansatormasidagi kerakli kuchlanishni ta\u2019minlay oladimi?<\/h2><p>Maxsus kuchlanish va maksimal kavitansiya o\u2018zaro bog\u2018liq ko\u2018rsatkichlar emas. Kichik sinov yukida nomerativ kuchlanishini yetkazadigan VLF manbai 0,1 Hz tezlikda uzun kabelda shu kuchlanishni saqlab qololmasligi mumkin.<\/p><p>Sinusoidal kapasitiv yuk uchun zaryadlash oqimini quyidagicha hisoblash mumkin:<\/p><pre class=\"wp-block-code\"><code>I = 2\u03c0fCV\n<\/code><\/pre><p>Qayerda:<\/p><ul><li><code>I<\/code>\u00a0RMS quvvatlanish holati<\/li>\n\n<li><code>f<\/code>\u00a0hertzda chastota<\/li>\n\n<li><code>C<\/code>\u00a0faradlarda umumiy tok aylanishi qanday?<\/li>\n\n<li><code>V<\/code>\u00a0RMS test voltaji<\/li><\/ul><p>Masalan, 57 kV RMS va 0,1 Hz chastotada 1,0 \u00b5F quvvat manbai taxminan quyidagicha quvvat sarflaydi:<\/p><pre class=\"wp-block-code\"><code>I = 2 \u00d7 \u03c0 \u00d7 0.1 \u00d7 1.0 \u00d7 10\u207b\u2076 \u00d7 57,000\nMen \u2248 0,0358 A yoki 35,8 mA RMS\n<\/code><\/pre><p>Bir xil kuchlanish va o\u2018tkazuvchanlikda ideal sinusli zaryadlash oqimi chastotaga proporsional bo\u2018ladi. 50 Hz quvvat manbai 0,1 Hz quvvat manbai bilan solishtirganda taxminan 500 baravar ko\u2018p zaryadlash oqimini talab qiladi; 60 Hz quvvat manbai esa taxminan 600 baravar ko\u2018p zaryadlash oqimini talab qiladi. Shuning uchun VLF uskunalari uzunligi 1000 km dan ortiq bo\u2018lgan magistral kabellar uchun an\u2019anaviy kuchlanish chastotali uskunalarga qaraganda ancha ko\u2018proq ko\u2018chirilishi mumkin.<\/p><p>Hisob-kitoblar ma\u02bclum bir testerning testni bajarishini isbotlamaydi. Ruxsat etilgan kombinatsiyani ko\u02bbrsatuvchi yuk jadvalini so\u02bbrang:<\/p><ul><li>Izolyatsiya kuchlanishi<\/li>\n\n<li>Foydalanish chastotasi<\/li>\n\n<li>Kabellarning o\u2018zaro bog\u2018lanishi<\/li>\n\n<li>To'lqin shakli<\/li>\n\n<li>Test davomiyligi yoki yuk aylanishi<\/li>\n\n<li>Atrof muhit va kiruvchi energiya chegaralari<\/li><\/ul><p>KV HIPOT maksimal chiqish kuchlanishi 30, 50, 60 va 80 kV bo\u2018lgan VLF konfiguratsiyalarini va 0,1, 0,05 va 0,02 Hz kabi tanlanishi mumkin bo\u2018lgan chastotalarni nashr etadi. Ushbu reytinglar konfiguratsiyaga bog\u2018liq. Masalan, nashr etilgan 60 kV konfiguratsiyasi har bir chastotada turli yuk qobiliyatini sanab o\u2018tadi; ushbu ko\u2018rsatkichlar boshqa voltaj konfiguratsiyasiga o\u2018tkazilmasligi kerak.<\/p><p>Qisqa muddatli rejalashtirilgan simulyatsiya uchun aniq KV HIPOT VLF tester konfiguratsiyasini ko\u2018rib chiqing va eng uzun rejim uchun kuchlanish-to\u2018lqin-saralash yuk konfiguratsiyasini tasdiqlang. Kabel 0,1 Hz dan oshib ketadigan bo\u2018lsa, chastotani shunchaki pasaytirishga yo\u2018l qo\u2018ymang: avval boshqaruv tartibi pastroq chastotani ruxsat etishini tasdiqlang va har qanday moslashuvni davomiylik yoki talqinni belgilang.<\/p><h2 class=\"wp-block-heading\">33 kV kabel tarmog\u2018ini qanday qilib xavfsiz tarzda tayyorlash va sinovdan o\u2018tkazish kerak?<\/h2><p>Raqamlashgan kuchlanish \u2013 bu tekshiruvning faqat bir qismi. Yong\u2018ochni noto\u2018g\u2018ri tanib olish, izolyatsiya qilish, zaryadlash yoki tekshiruvdan keyingi uzilishlar hisob-kitob xatosidan ko\u2018ra kattaroq xavf tug\u2018dirishi mumkin.<\/p><p><em>Kontroll ostidagi test tekshirishdan oldin tasdiqlangan izolyatsiya bosqichidan boshlanadi va timer o\u2018chirilganda tugaydi \u2014 timer o\u2018chirilganda emas.<\/em><\/p><p>Saytda bajariladigan ishlar protsedurasiga kamida quyidagi to\u2018xtash nuqtalarini kiritish kerak:<\/p><ol><li><strong>Ruxsatnomani va doirani tasdiqlang.<\/strong>\u00a0Sirkiyni aniqlang, maqsadni sinab ko\u2018ring, protsedurani, mas\u2018ul muhandisni, o\u2018zgartirish vakolatini va to\u2018xtatish mezonlarini aniqlang.<\/li>\n\n<li><strong>Har bir kabel tuguni va ulangan qurilmani aniqlang.<\/strong>\u00a0Bir qator diagrammasini, kabellar rejasini, fazalashni, ulagichlarni, tugatishlarni, transformatorlarni, to\u2018xtatuvchilarni, asbob transformatorlarini, elektronika va parallel toklar sistemasini ko\u2018rib chiqing.<\/li>\n\n<li><strong>Test sxemasini ajratib oling.<\/strong>\u00a0Eslatib o\u2018tamiz, egalar tomonidan belgilangan o\u2018chirish va bloklash\/tagout qoidalariga rioya qiling. Tasdiqlangan sinov sxemasi tarkibiga kirmaydigan asboblarni ajratib qo\u2018ying yoki himoyalang.<\/li>\n\n<li><strong>Elektr energiyasini yo\u2018qotish, ajratish va zaryadlashni isbotlang.<\/strong>\u00a0Har bir konduktorni sinovdan o\u2018tkazilguncha va sayt tartib-taomillariga muvofiq uni zaryadlanmagan holda qo\u2018yishguncha energiyali holatda saqlang.<\/li>\n\n<li><strong>Test setini va kontaktlarni tekshiring.<\/strong>\u00a0Modelni tasdiqlang, kalibrlash holatini, voltaj asosini, aksessuarlarni, qisqich holatini, ajratishlarni, yer aloqalarini, favqulodda to\u2018xtatishni va blokirovkalarni tasdiqlang.<\/li>\n\n<li><strong>Test zonasini tashkil eting.<\/strong>\u00a0To\u2018siqlar, ogohlantiruvchi belgilar, aloqa vositalari va energiya ta\u2019minoti uchun bitta mas\u2019ul shaxsdan foydalaning. Kabellarning uchlarini barcha joylarda nazorat ostida saqlang.<\/li>\n\n<li><strong>Ulanishlarni sozlang va mustaqil ravishda tasdiqlang.<\/strong>\u00a0Yuqori kuchlanishli simni ulash va metall ekranni, sinovdan o\u2018tkazilmagan fazalarni va ularga bog\u2018liq bo\u2018lgan o\u2018tkazuvchilarni tasdiqlangan usulga muvofiq zaryadlash kerakli darajada amalga oshiring.<\/li>\n\n<li><strong>Ruxsat etilgan sozlamalarni kiriting.<\/strong>\u00a0Darhol quvvatlanayotgan oqim oqimidan vaqtinchalik sinov elektr toki manbaini olib tashlashdan oldin, to'lqin shakli, chastota, maqsadli kuchlanish, ramp, davomiylik, chiqish chegaralari, kabelli kavitatsiya va hisobot identifikatorlarini tekshiring.<\/li>\n\n<li><strong>Kuchlaningiz va monitoring qiling.<\/strong>\u00a0Kuchlanishni faqat ruxsatnomaga asosan oshirish mumkin. Kutilmagan tok, kuchlanishning barqarorligi buzilishi, yorilish, g\u2018ayritabiiy shovqindan chiqish, tutun chiqishi, aloqa uzilishi, ob-havo o\u2018zgarishi yoki asbob himoyasi holati yuzaga kelganda to\u2018xtating.<\/li>\n\n<li><strong>Oqartirilgan va sezilarli darajada maydalanib ketgan.<\/strong>\u00a0Test setini to\u2018ldirish bosqichini yakunlashiga ruxsat bering, tasdiqlangan usul yordamida kuchlanishning yo\u2018qligini tasdiqlang, ko\u2018rinadigan zaminni qo\u2018llang va bu zaminni aylantirish yoki uzukni qayta ulangdan oldin kerakli vaqt davomida saqlang.<\/li><\/ol><p>Bizning xavfsiz VLF kabelli sinov tartibimiz to\u2018liqroq rejalashtirish va hisobot berish ro\u2018yxatini taqdim etadi. U hali ham mahalliy qoidalarga va uskunalar qo\u2018llanmasiga muvofiq ravishda sozlanishi kerak.<\/p><h2 class=\"wp-block-heading\">VLF sinov boshi yoki muvaffaqiyatsizlik haqida aslida nima ma'lumot beradi?<\/h2><p>Muvofiq VLF sinovdan o\u2018tkazish natijasida sinovdan o\u2018tkazilgan kabellar tizimi qayd etilgan sharoitlarda belgilangan to\u2018lqin shakli, kuchlanish va davomiylikni bardosh bera olganini anglatadi. Bu izolyatsiyaning har qanday nuqsonlardan xoli ekanligini tasdiqlamaydi, kelajakdagi xizmat ko\u2018rsatish muddatini kafolatlamaydi va barcha diagnostik sinovlarni almashtirmaydi.<\/p><p>Natijani aniq chegaralarda izohlash:<\/p><figure class=\"wp-block-table\"><table><thead><tr><th>Natija<\/th><th>U nimani qo\u2018llab-quvvatlaydi<\/th><th>U nima isbotlamaydi<\/th><th>To'g'ri keyingi qadam<\/th><\/tr><\/thead><tbody><tr><td>Hujjatli ruxsatnoma<\/td><td>Circuit tasdiqlangan sinov sharoitiga mos ravishda sinovdan o\u2018tkazildi.<\/td><td>Kamchiliklar yo\u2018q, PD yo\u2018q yoki qolgan hayot muddati kafolatlanadi<\/td><td>To\u2018liq ozod qilishni amalga oshiring, natijani tasdiqlang va egalarining xizmatga qaytish jarayonini kuzatib boring.<\/td><\/tr><tr><td>Kabellashish yoki yo\u2018lning uzilishi kabel tizimi nosozligi tufayli yuzaga kelgani tasdiqlandi<\/td><td>Circuit test sharoitiga bardosh berolmagan.<\/td><td>To'g'ri xato sababi yoki asosiy sabab<\/td><td>Sirkani to\u2018g\u2018ri sozlang, yozuvlarni saqlang, nosozlikni aniqlang va bartaraf qiling, keyin qayta sinovdan o\u2018tkazish uchun ruxsat olish<\/td><\/tr><tr><td>Asbob yo\u2018lida yoki barqaror harakatlanishda nuqsonlar<\/td><td>Rejalashtirilgan test bajarilmagan<\/td><td>Kabellarning shikastlanishi<\/td><td>Nima bo\u2018lganini aniqlashdan oldin yuk ko\u2018rsatkichini, ulashlarni, kirish quvvatini, sozlamalarni, muhitni va asbob ma\u2019lumotlarini tekshirib ko\u2018ring.<\/td><\/tr><tr><td>Operatsiya yo\u2018nalishining o\u2018zgarishi<\/td><td>Baqalar qabul qilinishi mumkin emas<\/td><td>Kutilayotgan tartib bo'yicha topshiriqni bajarish yoki muvaffaqiyatsizlikka uchragish<\/td><td>O\u2018zgarishni qayd qiling va muhandislik xulosasini oling; hisobotni tinchlantirmasdan tuzating.<\/td><\/tr><\/tbody><\/table><\/figure><p>Yosh kabel uchun, texnik xizmat ko\u2018rsatish qarorida \u201cpass\/fail\u201d natijasi yetarli bo\u2018lmaganda diagnostika tekshiruvlari qo\u2018llanilishi mumkin:<\/p><ul><li>Ishlatish\u00a0<strong>tan delta<\/strong>\u00a0agar savol keng ko\u2018lamli izolyatsiya holati, fazalarni taqqoslash yoki tendensiya haqida bo\u2018lsa.<\/li>\n\n<li>Ishlatish\u00a0<strong>parcial chiqish sinovlari<\/strong>\u00a0Agar masala faol lokalizatsiya qilingan chiqish va uning mumkin bo\u2018lgan joylashuvi haqida bo\u2018lsa.<\/li>\n\n<li>Bir foydalaning\u00a0<strong>oversheath test<\/strong>\u00a0agar savol asosiy izolyatsiya emas, balki himoya tashqi qobiq haqida bo\u2018lsa.<\/li>\n\n<li>Qolgan umr muddati haqida qaror qabul qilishdan oldin xizmat ko\u2018rsatish tarixini, avvalgi o\u2018lchovlarni, nosozliklar to\u2018g\u2018risidagi ma\u2019lumotlarni, yorug\u2018lik manbalarini va tugatish nuqtalarini ko\u2018rib chiqing.<\/li><\/ul><p>Oxirgi hisobot kabelni, sinovdan o\u2018tkazilgan fazani, qo\u2018shimcha aksessuarlarni, sinov apparatini va seriya raqamini, kalibrlash manbasini, to\u2018lqin shaklini, chastotani, kuchlanish asosini, maqsadli va erishilgan kuchlanishni, davomiylikni, kondensaturni, atrof-muhit sharoitlarini, uzilishlarni, kuzatuvlarni, ajralib chiqishni, zaryadlashni, zaryadlanishni qulaylashni va vakolatli yo\u2018l bilan chiqishni aniqlashi kerak.<\/p><h2 class=\"wp-block-heading\">Testni tanlash yoki tasdiqlashdan oldin nimalarni tasdiqlashingiz kerak?<\/h2><p>Quotatsiya so\u2018rash, usul bayonotini tasdiqlash yoki saytga borishdan oldin ushbu ro\u2018yxatdan foydalaning:<\/p><ul><li>\u00a0To\u02bbliq kabel ko\u02bbrsatkichi: U\u2080\/U (U\u2098)<\/li>\n\n<li>\u00a0Nominal tizim voltaji va zaryadlash tartibi<\/li>\n\n<li>\u00a0Izolyatsiya turi va kabel ishlab chiqaruvchisi<\/li>\n\n<li>\u00a0Kabellarning uzunligi, oqim o\u2018tkazuvchisi hajmi va qabul qiluvchi qismning kavitatsiyasi<\/li>\n\n<li>\u00a0Bosh va tugatish joylari soni va turlari<\/li>\n\n<li>\u00a0Yangilanish, qabul qilish yoki texnik xizmat ko\u2018rsatish maqsadlari<\/li>\n\n<li>\u00a0Muvofiq standart, nashr, egalar uchun tavsiflar va ishlab chiqaruvchi ko\u2018rsatmalar<\/li>\n\n<li>\u00a0Talab qilinadigan VLF shakli<\/li>\n\n<li>\u00a0Talab qilingan RMS, cho\u02bbqqi yoki boshqa voltaj asoslari<\/li>\n\n<li>\u00a0Ruxsat etilgan test chastotasi, davomiyligi, pasayish vaqtining uzunligi va safar qilish shartlari<\/li>\n\n<li>\u00a0Talab qilingan kuchlanish va chastotada sinov yukini o\u2018tkazish imkoniyati<\/li>\n\n<li>\u00a0Ishlash davri va atrofiy muhitdagi ishlash chegaralari<\/li>\n\n<li>\u00a0Kalibrlash doirasi va sertifikatning amal qilish muddati<\/li>\n\n<li>\u00a0Yerga qaytish, bir-biriga bog\u2018lash, favqulodda to\u2018xtatish va chiqish sozlamalari<\/li>\n\n<li>\u00a0O\u2018chirilishi yoki himoyalanishi kerak bo\u2018lgan uskunalarni<\/li>\n\n<li>\u00a0Talab qilinadigan hisobot maydonlari va natijani qabul qilish vakolatiga ega shaxs<\/li>\n\n<li>\u00a0Tan delta, PD yoki oversheath sinovlari zaruriyati<\/li><\/ul><p>Bu ma'lumotlarni uskunalarni yetkazib beruvchiga yuborish so'rashdan ko'ra ishonchliroqdir: \u201c33 kV kabeli uchun qaysi VLF testeri mos?\u201d Bizning qo\u2018llanmamizni ko\u2018rib chiqing\u00a0<a href=\"https:\/\/kvhipot.com\/uz\/what-are-the-best-vlf-hipot-testers-in-2026-for-your-buyers-guide\/\">to'g'ri VLF kabelni sinov apparatini tanlash<\/a>\u00a0ishlov berishga qaratilgan tekshiruv uchun.<\/p><h2 class=\"wp-block-heading\">Ko\u2018pincha beriladigan savollar<\/h2><h3 class=\"wp-block-heading\">57 kV RMS har doim 33 kV kabeli uchun to'g'ri VLF kuchlanishi bo'ladimi?<\/h3><p>Yo\u02bbq. Bu U\u2080 = 19 kV bo\u02bblgan kabellarga nisbatan 3U\u2080 hisoblanishi hisoblanadi. 18\/30 (36) kV belgilangan kabellarda 3U\u2080 da 54 kV RMS hosil bo\u02bbladi. 3U\u2080 qo\u02bbllanilishi kerakligi tasdiqlangan protsedura orqali aniqlanishi kerak.<\/p><h3 class=\"wp-block-heading\">80 kV VLF testeri avtomatik ravishda ushbu test uchun mosmi?<\/h3><p>Yo'q. 80 kV quvvati maksimal yoki RMS qiymati ekanligini, to'lqin shaklini va qurilmaning talab qilinadigan kuchlanish, chastota, qoplamasi va davomiyligi bo'yicha yukga chidamliligini tasdiqlang. 57 kV RMS sinov to'lqini taxminan 80,6 kV maksimal kuchga ega.<\/p><h3 class=\"wp-block-heading\">33 kV XLPE kabellari ustida DC hipot testeridan foydalana olamanmi?<\/h3><p>DC-ni faqat sinov to'plami mavjudligi sababli tanlamang. XLPE kabellar tizimi uchun kabel ishlab chiqaruvchisi, amaldagi standart, mulk egasi va tasdiqlangan tartib asosida ruxsat etilgan test usulini qo'llang. IEEE 400.1 hujjatida laminatli dielektrik AC kabellar tizimlarining DC sinovlari ko'rib chiqilgan, har bir XLPE simulyatori uchun universal DC usuli mavjud emas.<\/p><h3 class=\"wp-block-heading\">VLF sinov apparati suvli daraxtlarni yoki qisman zaryadsizlanishni aniqlay oladimi?<\/h3><p>Chidamlilik testi sxemaning belgilangan stressga bardosh berishini tekshiradi. Bu har bir suv daraxtining xususiyatlarini to\u2018g\u2018ridan-to\u2018g\u2018ri aniqlamaydi va PD qiymatini o\u2018lchamaydi. Ta\u2019mirlash bo\u2018yicha qaror diagnostik ma\u2019lumotlarni talab qilganda, tegishli tan delta yoki PD protsedurasidan foydalaning.<\/p><h3 class=\"wp-block-heading\">Uzoqroq kabelni sinab ko\u2018rish uchun tezlikni 0,1 Hz dan kamroqqa kamaytira olamanmi?<\/h3><p>Past chastota zaryadlash oqimini kamaytiradi va sinovdan o\u2018tkaziladigan qozonlikni oshirishi mumkin, biroq boshqaruvchi tartib bu chastotani ta\u2019minlashi va mos test sharoitlarini belgilashi kerak. Har qanday holatda ham, kichikroq o\u2018lchamdagi sinov qurilmasini ishni bajarish uchun o\u2018zgartirish mumkin emas.<\/p><h3 class=\"wp-block-heading\">Uch bosqich ham bir vaqtda sinab ko\u2018rilishi kerakmi?<\/h3><p>Qorayilgan MV kabelining fazalari odatda alohida sinovdan o\u2018tkaziladi; metall qatlam va sinovdan o\u2018tkazilmagan o\u2018tkazuvchilar tasdiqlangan ulanish diagrammasiga muvofiq zaryadlanadi. Kabelning konstruksiyasi va ulanadigan jihozlar tartibini o\u2018zgartirishi mumkin, shuning uchun umumiy diagrammadan ko\u2018ra vakolatli tartibda harakatlaning.<\/p><h3 class=\"wp-block-heading\">VLF to\u2018lashi kablarning yana ko\u2018p yillar xavfsiz bo\u2018lishini anglatadimi?<\/h3><p>Yo'q. Bu test qilingan sxem qayd etilgan sinov sharoitidan omon qolganini anglatadi. Qolgan ishlash muddati to'g'risidagi qarorlar xizmat ko'rsatish tarixini, nosozlikning oqibatlarini, jihozlarning texnik xususiyatlarini, tendensiya ma'lumotlarini va aktiv egalarining belgilagan har qanday diagnostika tekshiruvlarini talab qiladi.<\/p><h3 class=\"wp-block-heading\">33 kV kabeli qancha vaqt sinovdan o\u2018tkazilishi kerak?<\/h3><p>Hozirgi tartib-taomillarida kabel uchun belgilangan vaqt, shakli, hayot aylanishi bosqichi va sinov ob'ektivini qo'llang. \u201c15 dan 60 minutgacha\u201d umumiy sozlash sifatida foydalanish uchun juda keng ko'rsatkich bo'lib, uni tegishli qator va shartlarni aniqlamasdan qo'llash mumkin emas.<\/p>","protected":false},"excerpt":{"rendered":"<p>Har bir 33 kV kabeli uchun universal sinov kuchlanishi mavjud emas. Agar nomlovchi belgida 19\/33 (36) kV ko\u02bbrsatilgan bo\u02bblsa va tasdiqlangan tartibda 3U\u2080 sinusoidal VLF belgilangan bo\u02bblsa, hisoblangan daraja 57 kV RMS yoki taxminan 81 kV cho\u02bbqqi kuchlanishi bo\u02bbladi. 18\/30 (36) kV kabeli boshqacha natija keltirib chiqaradi.<\/p>","protected":false},"author":1,"featured_media":6668,"comment_status":"open","ping_status":"open","sticky":false,"template":"","format":"standard","meta":{"_seopress_robots_primary_cat":"none","_seopress_titles_title":"","_seopress_titles_desc":"","_seopress_robots_index":"","footnotes":""},"categories":[40],"tags":[],"_links":{"self":[{"href":"https:\/\/kvhipot.com\/uz\/wp-json\/wp\/v2\/posts\/6665"}],"collection":[{"href":"https:\/\/kvhipot.com\/uz\/wp-json\/wp\/v2\/posts"}],"about":[{"href":"https:\/\/kvhipot.com\/uz\/wp-json\/wp\/v2\/types\/post"}],"author":[{"embeddable":true,"href":"https:\/\/kvhipot.com\/uz\/wp-json\/wp\/v2\/users\/1"}],"replies":[{"embeddable":true,"href":"https:\/\/kvhipot.com\/uz\/wp-json\/wp\/v2\/comments?post=6665"}],"version-history":[{"count":1,"href":"https:\/\/kvhipot.com\/uz\/wp-json\/wp\/v2\/posts\/6665\/revisions"}],"predecessor-version":[{"id":6669,"href":"https:\/\/kvhipot.com\/uz\/wp-json\/wp\/v2\/posts\/6665\/revisions\/6669"}],"wp:featuredmedia":[{"embeddable":true,"href":"https:\/\/kvhipot.com\/uz\/wp-json\/wp\/v2\/media\/6668"}],"wp:attachment":[{"href":"https:\/\/kvhipot.com\/uz\/wp-json\/wp\/v2\/media?parent=6665"}],"wp:term":[{"taxonomy":"category","embeddable":true,"href":"https:\/\/kvhipot.com\/uz\/wp-json\/wp\/v2\/categories?post=6665"},{"taxonomy":"post_tag","embeddable":true,"href":"https:\/\/kvhipot.com\/uz\/wp-json\/wp\/v2\/tags?post=6665"}],"curies":[{"name":"wp","href":"https:\/\/api.w.org\/{rel}","templated":true}]}}